International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

EJGF — SF6 combined current and voltage transformer, 245–550 kV

EJGF SF6 combined current and voltage transformer for 245–550 kV substations, primary current up to 5000 A. The VT is located in the upper part and the CT core in the lower part of the head.

Rated voltage
245–550 kV
Primary current
up to 5000 A
Short-time thermal current
up to 80 kA / 3 s
Dynamic withstand current
up to 200 kA

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

SF6 insulation, polymer insulator, monitored gas density. Short-time thermal current up to 80 kA for 3 s, dynamic current up to 200 kA. Up to 8 CT windings and up to 5 VT windings. CT accuracy classes 0.1–3, P, PR, PX, TPS, TPX, TPY, TPZ; VT classes 0.1–3, 3P and 6P. A common CT and VT housing reduces the number of units in the switchyard.

Technical specifications

Rated voltage245–550 kV
Primary currentup to 5000 A
Short-time thermal currentup to 80 kA / 3 s
Dynamic withstand currentup to 200 kA
CT accuracy classes0.1–3; P; PR; PX; TPS; TPX; TPY; TPZ
VT accuracy classes0.1–3; 3P; 6P
Windingsup to 8 CT windings, up to 5 VT windings
InsulationSF6

Replacement for

no direct analog (combined CT + VT units were not produced in series); pairs ТРГ-220 + ЗНОГ-220, ТРГ-500 + НДЕ-500-72

selected by purpose and main parameters, please confirm with our manager

Request a price and lead time

EJGF — SF6 combined current and voltage transformer, 245–550 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8504 31 21 00
8504 31 29 00
HS, 6 digits8504 31
CN (EU)8504 31 21
8504 31 29
HTSUS (USA)8504 31 20 00
China customs tariff8504 31 10 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

How many secondary windings can the EJGF have?

Up to 8 current transformer windings and up to 5 voltage transformer windings.

What accuracy classes do the CT and VT have?

The CT is available in classes 0.1–3, P, PR, PX, TPS, TPX, TPY, TPZ. The VT in classes 0.1–3, 3P and 6P.

What networks and short-circuit currents is the unit rated for?

For 245–550 kV substations with a primary current up to 5000 A. Thermal withstand 80 kA / 3 s, dynamic 200 kA.