CTS 12, CTS 25, CTS 38 — indoor post-type current transformers 12–38.5 kV
CTS 12, CTS 25 and CTS 38 are post-type instrument current transformers with cast epoxy insulation for indoor medium-voltage switchgear at 12/17.5, 24 and 38.5 kV. They are installed in revenue and technical metering circuits and in relay protection circuits. Primary current from 5 A to 3200 A, secondary 5 A or 1 A.
- Voltage
- 12/17.5 kV (CTS 12), 24 kV (CTS 25), 38.5 kV (CTS 38)
- Primary current
- 5–3200 A (CTS 12), 5–2500 A (CTS 25, CTS 38.41W), 5–600 A (X versions)
- Secondary current
- 5 A or 1 A, combinations
- Accuracy classes
- measurement 0.2; 0.5; 0.2S; 0.5S; 1; 3; protection 5P, 10P, PX
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The range consists of three groups. At 12/17.5 kV there are CTS 12, CTS 12.L, CTS 12.LW, CTS 12.W and CTS 12.G, at 24 kV CTS 25, CTS 25.1, CTS 25.SW, CTS 25X and the Sch, B, C versions, at 38.5 kV CTS 38, CTS 38X and CTS 38.41W. The primary current of CTS 12 reaches 3200 A, CTS 25 and CTS 38.41W up to 2500 A, CTS 38 up to 2000 A, X versions up to 600 A. Rated burden 2.5–60 VA.
Measuring windings are made in accuracy classes 0.2, 0.5, 0.2S, 0.5S, 1 and 3, protection windings in classes 5P, 10P and PX. The stated class is kept within 25–100 % of the rated burden. Secondary current is 5 A or 1 A, a combination is possible. For CTS 25 the manufacturer gives a short-time thermal current up to 80 kA for 1 s (31.5 kA for 3 s), a dynamic current up to 200 kA and a continuous thermal current of 120 % In.
The primary winding is single-turn or multi-turn. The transformation ratio is changed on both the secondary and the primary side; for this the corresponding terminals are connected with two M8 screw links, and the screws and links are included in the set. The secondary cores are wound from grain-oriented electrical steel or from permalloy, and their number is from 1 to 4 at the customer request. All active parts are cast in epoxy compound, which works both as insulation and as the supporting structure. Enlarged versions such as CTS 12.LW (height 210 mm, weight 29 kg) have higher short-circuit withstand, greater burden and a higher safety factor.
CTS 12, CTS 25 and CTS 25X can have a built-in voltage indicator. A capacitive divider is cast into the body, and a cable interface and a VDS indicator of class HR according to ČSN EN 61243-5 with components from Georg Jordan GmbH are connected to the Ck terminal in the terminal box. The state voltage absent is indicated below 10 % Un, voltage present above 45 % Un.
The mounting position is arbitrary, the transformer is fixed with four screws through holes in the base. For replacing old transformers of various manufacturers, CTS are supplied on adapted bases with the same mounting dimensions. Testing was carried out according to ČSN EN/IEC 61869-1 and 61869-2. The transformers are installed in 6–35 kV switchgear cells of distribution networks and industrial substations.
Technical specifications
| Voltage | 12/17.5 kV (CTS 12), 24 kV (CTS 25), 38.5 kV (CTS 38) |
|---|---|
| Primary current | 5–3200 A (CTS 12), 5–2500 A (CTS 25, CTS 38.41W), 5–600 A (X versions) |
| Secondary current | 5 A or 1 A, combinations |
| Accuracy classes | measurement 0.2; 0.5; 0.2S; 0.5S; 1; 3; protection 5P, 10P, PX |
| Burden | 2.5–60 VA |
| Cores | 1–4 (CTS 12.LW) |
| Ratio change | on the primary and secondary side |
| Option | built-in capacitive divider for voltage indicator (VDS, IEC 61243-5) |
| Standards | IEC 61869-1, IEC 61869-2 (ČSN EN) |
Replacement for
ТОЛ-10, ТЛО-10, ТПЛ-10, ТЛК-10, ТЛМ-10, ТПОЛ-10; ТОЛ-20, ТОЛ-35, ТЛК-35
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
CTS 12, CTS 25, CTS 38 — indoor post-type current transformers 12–38.5 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 8504 31 29 00 |
|---|---|
| HS, 6 digits | 8504 31 |
| CN (EU) | 8504 31 29 |
| HTSUS (USA) | 8504 31 40 35 |
| China customs tariff | 8504 31 10 00 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
For which voltage classes are CTS transformers made?
CTS 12 for 12/17.5 kV, CTS 25 for 24 kV, CTS 38 for 38.5 kV. All are intended for indoor switchgear.
Which accuracy classes are available for the windings?
For measurement 0.2, 0.5, 0.2S, 0.5S, 1 and 3, for protection 5P, 10P and PX. The class is kept within 25–100 % of the rated burden.
Can CTS replace an old transformer of another manufacturer?
Yes, CTS are supplied on adapted bases with the same mounting dimensions as the types being replaced.
Similar equipment from other manufacturers