International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

OBCT, EGCT, BGCT, DBCT, SBCT, RELV and CRT current transformers for metering and protection

This family of current transformers for protection and commercial metering includes built-in bushing, generator, surface-mounted, zero-sequence and CRT metering types. Accuracy classes start at 0.15S, with burdens of B0.1 to B1.8 or 2.5 to 45 VA.

Purpose
protection and metering, metering
Types
built-in bushing (oil-filled, dry), generator, surface-mounted, zero-sequence, metering
Primary current OBCT, DBCT
above 8000 A
Metering class OBCT
0.15S…2.4 / 0.2S…5.0

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

These current transformers are used in power generation, distribution networks and industrial processes to measure current, meter electricity, provide protection, detect faults and support operational control. Most types are built for a specific application, and their characteristics can be matched to a transformer already installed on site.

The OBCT is fitted inside oil-filled equipment over the bushing neck. It works with primary currents above 8000 A, has cores with an air gap for controlling residual magnetism and transient response, and is made with one, two or several ratios (SR, DR, MR). The dry-type DBCT is also mounted inside equipment, under an outer cover or in a sealed cabinet, with primary currents above 8000 A and secondary leads terminated with terminals or flexible wires.

The EGCT and BGCT are intended for generator bushings. The EGCT is compound-filled for heavy operating conditions and has a Sky Grey (ANSI 70) housing. The BGCT is board-mounted and can be supplied as ready-made multi-core assemblies, which shortens downtime during emergency repairs. Both types are made with a single ratio (SR) only. Windings can have extra test taps, and conduit openings are threaded up to 1.5 inch NPT or unthreaded up to 52 mm. The rated current factor is up to 1.0 at 55°C.

The SBCT is installed externally by slipping it over the bushing. It is supplied with earthing shields and site mounting kits, and a two-core design is possible with 3 kV insulation between the cores. The RELV is a rectangular, cast, surface-mounted zero-sequence transformer for low-voltage networks that detects current imbalance. The CRT metering transformers have a 5.5 inch (140 mm) window and dimensions of 8.25 x 9.84 x 2.88 inch (210 x 250 x 73 mm). The CRT-15E holds an error of +/- 0.15% from 1% of rated current up to the rated current factor, the CRT-15S meets class 0.15S from 5% of rated current, the CRT-15 meets class 0.15 and the CRT-3 meets class 0.3.

Technical specifications

Purposeprotection and metering, metering
Typesbuilt-in bushing (oil-filled, dry), generator, surface-mounted, zero-sequence, metering
Primary current OBCT, DBCTabove 8000 A
Metering class OBCT0.15S…2.4 / 0.2S…5.0
Metering class EGCT, BGCT0.15S…0.6 (IEEE) / 0.2S…0.5 (IEC)
BurdenB0.1…B1.8 / 2.5…45 VA
RatiosSR, DR, MR (OBCT); SR (EGCT, BGCT)
Rated current factor EGCT, BGCTup to 1.0 at 55°C
Conduit openingsthreaded up to 1.5 inch NPT or unthreaded up to 52 mm
Insulation between cores SBCT3 kV
CRT window5.5 inch (140 mm)
CRT dimensions8.25 x 9.84 x 2.88 inch (210 x 250 x 73 mm)
Accuracy CRT-15E / CRT-15S+/- 0.15% from 1% / from 5% of rated
Housing colourSky Grey (ANSI 70), black

Part numbers

Show all part numbers (10)

OBCT, EGCT, BGCT, DBCT, SBCT, RELV, CRT-15E, CRT-15S, CRT-15, CRT-3

Request a price and lead time

OBCT, EGCT, BGCT, DBCT, SBCT, RELV and CRT current transformers for metering and protection. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which type suits currents above 8000 A?

The built-in bushing OBCT for oil-filled equipment and the dry-type DBCT are both rated for primary currents above 8000 A.

Can a transformer already installed on a generator be replaced?

Yes. EGCT and BGCT are made to suit the characteristics of an existing transformer, and BGCT can be supplied as ready-made multi-core assemblies.

What accuracy do the CRT metering transformers have?

The CRT-15E and CRT-15S hold +/- 0.15% from 1% or 5% of rated current respectively, the CRT-15 meets class 0.15 and the CRT-3 meets class 0.3.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides