YBW / ZGS / TBYDB 10–35 kV packaged transformer substations and 10–110 kV mobile substations
YBW, ZGS and TBYDB are packaged transformer substations of 10–35 kV rated 2500–7000 kVA and mobile substations of 10–110 kV on semi-trailers. The packaged substations supply consumers, solar and wind plants, and railway signalling.
- American type
- ZGS18-Z.G-3150/35: 3150 kVA, (35 ±2×2.5 %)/0.8 kV, bayonet and backup fuses
- European type
- YBW-24-5000: 5000 kVA, (22 ±2×2.5 %)/0.63/0.63 kV
- For renewables
- YBWL18-40.5/1.14-7000 (7 MVA, aluminium); YBPT1-38.5/0.8-3150 (IP54)
- Railway
- TZBW-12/0.4-2500: 10/0.4 kV, SF6 gas-insulated switchgear, UPS, remote control; −45…+70 °C, up to 5000 m
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The manufacturer produces packaged transformer substations and mobile substations on trailers. In a packaged substation a power transformer, an HV compartment with switchgear, an LV compartment, metering, compensation and internal connections are assembled in one enclosure. They supply consumers or step up the voltage of inverters and wind turbines at renewable energy stations. The network frequency is 50 or 60 Hz.
The American-type substation ZGS18-Z.G-3150/35, rated 3150 kVA ((35 ±2×2.5 %)/0.8 kV, Dy11, short-circuit voltage 7 %), is built as a monoblock. The transformer tank contains a load-break switch, bayonet and backup fuses and a tap changer. It is compact and light, with low losses and partial discharge, and is most often installed at solar plants. The European-type substation YBW-24-5000, rated 5000 kVA ((22 ±2×2.5 %)/0.63/0.63 kV, Dy11y11), consists of HV and LV compartments, a transformer and a thermally insulated enclosure with condensation protection. Cabinets and the transformer are selected for the project, and per the manufacturer the model is aimed at solar and wind plants in countries with 20 kV networks.
The Chinese-type YBWL18-40.5/1.14-7000 rated 7 MVA ((37 ±2×2.5 %)/1.14 kV) has an all-aluminium low-carbon enclosure, digital monitoring and high corrosion resistance. The integrated YBPT1-38.5/0.8-3150 for wind and solar plants (3150 kVA, 38.5/0.8 kV) is assembled in a galvanised steel enclosure with degree of protection IP54, with a no-load loss of up to 2.4 kW and a short-circuit loss of up to 21.9 kW.
The railway TZBW-12/0.4-2500 supplies automatic block signalling devices and longitudinal lines. It includes 10 kV SF6 gas-insulated switchgear, a circuit breaker, transformers, a dual-feeder monitoring device, a 10 kV fault clearing device and a UPS. The substation operates at temperatures of −45…+70 °C at altitudes up to 5000 m.
Mobile TBYDB substations carry primary and secondary equipment on one or several semi-trailers and quickly restore power supply during outages and reconstruction. The 110 kV versions are fitted with the SZ-40000/110 transformer (40 MVA, (110 ±8×1.25 %)/10.5 kV, no-load loss 21 kW and short-circuit loss 140 kW) or the three-winding SSZ-20000/110 rated 20 MVA (110/38.5/10.5 kV). There are versions for 35 kV (TBYDB-SZ-10000/35) and 10 kV (TBYDB-S-20000/10, 10.5/6.3 kV). All substations are assembled and tested at the factory and designed in 3D with seismic calculation.
Technical specifications
| American type | ZGS18-Z.G-3150/35: 3150 kVA, (35 ±2×2.5 %)/0.8 kV, bayonet and backup fuses |
|---|---|
| European type | YBW-24-5000: 5000 kVA, (22 ±2×2.5 %)/0.63/0.63 kV |
| For renewables | YBWL18-40.5/1.14-7000 (7 MVA, aluminium); YBPT1-38.5/0.8-3150 (IP54) |
| Railway | TZBW-12/0.4-2500: 10/0.4 kV, SF6 gas-insulated switchgear, UPS, remote control; −45…+70 °C, up to 5000 m |
| Mobile 110 kV | TBYDB-SZ-40000/110 (40 MVA, 110/10.5 kV), TBYDB-SSZ-20000/110 (20 MVA, 110/38.5/10.5 kV) |
| Mobile 35/10 kV | TBYDB-SZ-10000/35, TBYDB-S-20000/10 (10.5/6.3 kV) |
| Frequency | 50/60 Hz |
Request a price and lead time
YBW / ZGS / TBYDB 10–35 kV packaged transformer substations and 10–110 kV mobile substations. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 8537 20 91 00 |
|---|---|
| HS, 6 digits | 8537 20 |
| CN (EU) | 8537 20 91 |
| HTSUS (USA) | 8537 20 00 00 |
| China customs tariff | 8537 20 90 00 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
Which packaged substation is offered for solar plants?
The monoblock ZGS18-Z.G-3150/35 rated 3150 kVA with voltages of (35 ±2×2.5 %)/0.8 kV and a short-circuit voltage of 7 %. For wind and solar plants there is also the integrated YBPT1-38.5/0.8-3150 in an IP54 enclosure.
In what conditions does the railway substation TZBW-12/0.4-2500 operate?
At temperatures of −45…+70 °C at altitudes up to 5000 m. It has 10 kV SF6 gas-insulated switchgear and a UPS to supply automatic block signalling.
Which transformers are fitted in 110 kV mobile substations?
The SZ-40000/110 rated 40 MVA with voltages of (110 ±8×1.25 %)/10.5 kV or the three-winding SSZ-20000/110 rated 20 MVA. The equipment is placed on one or several semi-trailers.