TSBI concrete packaged substation with indoor access, up to 2 × 2000 kVA
The TSBI is a concrete substation with a service corridor inside. It is designed for a 12–36 kV RMU and two transformers up to 2000 kVA each, oil-filled or dry-type.
- Medium voltage
- 12–36 kV
- Transformer
- oil-filled or dry-type, up to 2 × 2000 kVA
- LV switchboard
- HMS or CMS
- Material
- concrete
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The transformers are oil-filled or dry-type, up to 2 × 2000 kVA in total. On the LV side an HMS or CMS LV switchboard is installed. Degree of protection is IP23D, arc resistance is IAC-AB 20 kA 1 s according to IEC 62271-202. The internal corridor allows equipment to be serviced in any weather, with personnel working inside a closed concrete enclosure.
Technical specifications
| Medium voltage | 12–36 kV |
|---|---|
| Transformer | oil-filled or dry-type, up to 2 × 2000 kVA |
| LV switchboard | HMS or CMS |
| Material | concrete |
| Degree of protection | IP23D |
| Arc resistance | IAC-AB 20 kA 1 s |
| Standard | IEC 62271-202 |
Request a price and lead time
TSBI concrete packaged substation with indoor access, up to 2 × 2000 kVA. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 8537 20 91 00 |
|---|---|
| HS, 6 digits | 8537 20 |
| CN (EU) | 8537 20 91 |
| HTSUS (USA) | 8537 20 00 20 |
| China customs tariff | 8537 20 90 00 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
What transformer power does the TSBI have?
Two transformers up to 2000 kVA each, oil-filled or dry-type.
What medium voltage is the TSBI designed for?
An RMU for 12–36 kV, with arc resistance IAC-AB 20 kA 1 s.
How is the substation serviced?
From the inside, from a service corridor in a concrete enclosure with degree of protection IP23D.
Similar equipment from other manufacturers