MRw-b(pp), packaged transformer substation in a concrete enclosure with an internal service corridor, 20/0.4 kV, up to 2×630 / 1000 kVA

The MRw-b(pp) container-type packaged substation in a concrete enclosure is serviced from an internal corridor and is designed for a transformer of up to 630 or 1000 kVA or for 2×630 kVA. MV voltage up to 25 kV, LV up to 0.69–0.8 kV. In special versions the transformer rating reaches 4000 kVA.

Transformer rating
up to 630 kVA, 1000 kVA, 2×630 kVA (in special versions up to 4000 kVA)
MV voltage
up to 25 kV
LV voltage
up to 0.69–0.8 kV
Rated current of MV / LV switchgear
630 A / up to 1600 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The versions MRw-b1, MRw-b2, MRw-b(pp) -3/-4 and the two-transformer 20/2×630 are produced. Inside are installed MV and LV switchgear of the manufacturer's own production with a rated current of 630 A and up to 1600 A. Internal arc resistance is IAC-AB-16 kA-1 s, the degree of protection is IP 23D, and IP 43 to order. The enclosure consists of three monolithic elements of precast reinforced concrete C30/37. The substation works in cable and cable-overhead medium voltage networks and complies with PN-EN 62271-202.

Technical specifications

Transformer ratingup to 630 kVA, 1000 kVA, 2×630 kVA (in special versions up to 4000 kVA)
MV voltageup to 25 kV
LV voltageup to 0.69–0.8 kV
Rated current of MV / LV switchgear630 A / up to 1600 A
Internal arc resistanceIAC-AB-16 kA-1 s
Degree of protectionIP 23D (option IP 43)
Enclosureprecast reinforced concrete C30/37, three monolithic elements
StandardPN-EN 62271-202

Request a price and lead time

MRw-b(pp), packaged transformer substation in a concrete enclosure with an internal service corridor, 20/0.4 kV, up to 2×630 / 1000 kVA. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8537 20 91 00
HS, 6 digits8537 20
CN (EU)8537 20 91
HTSUS (USA)8537 20 00 20
China customs tariff8537 20 90 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

What transformer rating can be installed in MRw-b(pp)?

Up to 630 kVA, 1000 kVA or 2×630 kVA in the two-transformer version. In special versions up to 4000 kVA.

What voltages and currents are the substation switchgear rated for?

MV up to 25 kV and 630 A, LV up to 0.69–0.8 kV and up to 1600 A.

What is the arc resistance and degree of protection of the enclosure?

Internal arc resistance is IAC-AB-16 kA-1 s, the degree of protection is IP 23D, and IP 43 to order.