JUPITER-9000K / STS-6000K/3000K / JUPT-11000K/7000K/3000K — packaged transformer substation, 3.4–11 MVA
Packaged transformer substations JUPITER, STS and JUPT rated 3.4–11 MVA with 10–35 kV output. They connect SUN2000 inverters and PCS LUNA2000 to the medium voltage network and transmit monitoring data from the transformer, the LV switchboard and the MV switchgear.
- Power
- JUPITER-9000K: 9000 kVA; STS: 6800 / 3400 kVA; JUPT: 11 040 / 7360 / 3680 kVA at 40 °C
- Voltage
- input 800 V (JUPITER/STS) or 1000 V (JUPT), output 10–35 kV
- Transformer
- oil-filled, ONAN/ONAF/KNAN, Dy11-y11, EN 50588-1 / EN 50708
- MV switchgear
- SF6 or SF6-free (JUPT), vacuum circuit breaker
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The JUPITER-9000K is rated 9000 kVA, the STS 6800 or 3400 kVA, and the JUPT 11 040, 7360 or 3680 kVA at 40 °C. Input is 800 V for the JUPITER and STS, 1000 V for the JUPT. The transformer has ONAN, ONAF or KNAN cooling, vector group Dy11-y11 and complies with EN 50588-1 and EN 50708. The MV switchgear has a vacuum circuit breaker with SF6 or SF6-free insulation (JUPT). Assembled and tested at the factory in a 20 ft HC container.
Technical specifications
| Power | JUPITER-9000K: 9000 kVA; STS: 6800 / 3400 kVA; JUPT: 11 040 / 7360 / 3680 kVA at 40 °C |
|---|---|
| Voltage | input 800 V (JUPITER/STS) or 1000 V (JUPT), output 10–35 kV |
| Transformer | oil-filled, ONAN/ONAF/KNAN, Dy11-y11, EN 50588-1 / EN 50708 |
| MV switchgear | SF6 or SF6-free (JUPT), vacuum circuit breaker |
| Version | 20 ft HC container, factory assembly and testing |
Request a price and lead time
JUPITER-9000K / STS-6000K/3000K / JUPT-11000K/7000K/3000K — packaged transformer substation, 3.4–11 MVA. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 8537 20 91 00 |
|---|---|
| HS, 6 digits | 8537 20 |
| CN (EU) | 8537 20 91 |
| HTSUS (USA) | 8537 20 00 40 |
| China customs tariff | 8537 20 90 00 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
What is the power rating of each substation model?
JUPITER-9000K is 9000 kVA, STS is 6800 and 3400 kVA, and JUPT is 11 040, 7360 and 3680 kVA at 40 °C.
What output voltage does the substation deliver?
Output is 10–35 kV, with input of 800 V for the JUPITER and STS or 1000 V for the JUPT.
What transformer is installed in the substation?
An oil-filled unit with ONAN, ONAF or KNAN cooling, vector group Dy11-y11, complying with EN 50588-1 and EN 50708.